DIRECTOR'S OFFICE CONSTRUCTION SAFETY STANDARDS Filed with the Secretary of State on November 15, 1989 These rules take effect 15 days after filing with the Secretary of State |
| (By authority conferred on the construction safety standards commission by sections 19 and 21 of Act No. 154 of the Public Acts of 1974, as amended, being §§408.1019 and 408.1021 of the Michigan Compiled Laws) |
|
PART
2. MASONRY WALL BRACING
|
| R 408.40201 | Scope |
| R 408.40202 | Applicability |
| R 408.40203 | Definitions; C to U |
| R 408.40204 | Maximum unsupported height tables |
| R 408.40205 | Wind velocity; determination by qualified person |
| R 408.40206 | Wall bracing design |
| R 408.20207 | Typical wall bracing system |
| R 408.20208 | Signing |
| R 408.20209 | Inspection |
| R 408.20210 | Wall bracing system, responsibility for installation; responsibility for replacing system and danger signs |
| R 408.40201 Scope. | |
| Rule 201. | This part pertains to the temporary bracing of unsupported masonry walls during construction which are exposed to wind forces. |
| Return to Table of Contents | |
| R 408.40202 Applicability. | |
| Rule 202. | This part is designed to ensure a safe work environment for all personnel on the construction site through the use of temporary bracing of unsupported masonry walls. The requirements of this part are as follows: |
| (a) | Identifying masonry walls requiring temporary bracing (R 408.40204(1)). |
| (b) | Proposing an acceptable temporary bracing system (R 408.40207). |
| (c) | Vacating the collapse area during winds of 35 mph or more (R 408.40204(9) and R 408.40205). |
| (d) | Standard sign requirements for collapse areas (R 408.40208), which are all designed to prevent on-site injury. While winds of more than 35 mph may cause collapse of walls braced in accordance with this part, compliance with all of the other provisions of this part will ensure that no one will be within the collapse area. |
| Return to Table of Contents | |
| R 408.40203 Definitions; C to U. | |
| Rule 203. (1) | "Cavity
wall" means a masonry wall with a continuous insulated or uninsulated air space of 2 to 4 1/2 inches between wythes that are connected with rigid metal ties. |
| (2) | "Collapse area" means that area which is within the height of the wall, plus 4 feet, measured at right angles to the wall on both sides. |
| (3) | "Composite wall" means a bonded masonry wall with 2 or more wythes of different masonry units. |
| (4) | "Qualified person" means a person who, by knowledge, training, or experience, has the ability to solve or resolve problems relating to the subject matter or the work. |
| (5) | "Single wythe hollow masonry" means a masonry wall 1 unit in thickness made up of units with bearing surfaces that are less than 75% solid. |
| (6) | "Solid masonry unit" means a masonry unit with bearing surfaces that are 75% or more solid. |
| (7) | "Unsupported masonry wall" means a masonry wall that has not obtained its final lateral stability from design features when required, such as roofs, floors, buttresses, crosswalls, and piers. |
| Return to Table of Contents | |
|
TABLE
1
|
|
|
Exposure
Selection
|
|
|
Exposure
|
Example
|
|
A
|
Center of large cities and very rough hilly terrain. |
|
B
|
Suburban areas, towns, city outskirts, wooded areas, and rolling terrain. |
|
C
|
Flat, open country, open flat coastal belts, and grasslands. |
| (3) | Exposure A shall not be used in Michigan. |
| (4) | Table 2 reads as follows: |
|
TABLE
2
|
|||||
|
Single
Wythe Hollow Masonry
|
|||||
| Width of Wall | Minimum Weight psf | Maximum Unsupported Height | |||
| Exposure B | Exposure C | ||||
| (1) | (2) | (1) | (2) | ||
| 4 in. | 25 | 6 ft. | (2 ft.)* | 6 ft. | (1 ft.)* |
| 6 in. | 34 | 6 ft. | (5 ft.)* | 6 ft. | (2.5 ft.)* |
| 8 in. | 40 | 7 ft. | (7 ft.)* | 6 ft. | (4 ft.)* |
| 10 in. | 48 | 10 ft. | (10 ft.)* | 6 ft. | (6 ft.)* |
| 12 in. | 56 | 14 ft. | (14 ft.)* | 9 ft. | (9 ft.)* |
| 16 in. | 75 | 24 ft. | (24 ft)* | 16 ft. | (16 ft.)* |
|
*See
subrule (8) of this rule.
|
|||||
| (5) | Table 3 reads as follows: |
| TABLE 3 | |||||
| Solid Brick Walls | |||||
| Width of Wall | Minimum Weight psf | Maximum Unsupported Height | |||
| Exposure B | Exposure C | ||||
| (1) | (2) | (1) | (2) | ||
| 4 in. | 40 | 6 ft. | (3 ft.)* | 6 ft. | (2 ft.)* |
| 8 in. | 80 | 12 ft. | (12 ft.)* | 8 ft. | (8 ft.)* |
| 12 in. | 120 | 20 ft. | (20 ft.)* | 19 ft. | (19 ft.)* |
| 16 in. | 160 | 26 ft. | (26 ft.)* | 26 ft. | (26 ft.)* |
| *See subrule (8) of this rule. | |||||
| (6) | Table 4 reads as follows: |
| TABLE 4 | |||||||
| Composite
Walls--4-inch Brick and Hollow Block Units (Various Widths) |
|||||||
| Width of Wall Total | Brick | Block | Min. Weight psf | Maximum Unsupported Height | |||
| Exposure B | Exposure C | ||||||
| (1) | (2) | (1) | (2) | ||||
| 8 in. | 4 in. | 4 in. | 65 | 9 ft. | (9 ft.)* | 6 ft. | (5 ft.)* |
| 10 in. | 4 in. | 6 in. | 74 | 13 ft. | (13 ft.)* | 9 ft. | (9 ft.)* |
| 12 in. | 4 in. | 8 in. | 80 | 16 ft. | (16 ft.)* | 11 ft. | (11 ft.)* |
| 14 in. | 4 in. | 10 in. | 88 | 19 ft. | (19 ft.)* | 14 ft. | (14 ft.)* |
| 16 in. | 4 in. | 12 in. | 96 | 26 ft. | (26 ft.)* | 17 ft. | (17 ft.)* |
| *See subrule (8) of this rule. | |||||||
| (7) | Table 5 reads as follows: |
|
TABLE
5
|
||||||
|
Cavity
Walls--4-inch Brick and Hollow Block Units (Various Widths)
|
||||||
|
Wall
Selection
Brick + Block |
Minimum
Weight psf
|
Maximum
Unsupported Height
|
||||
|
Exposure
B
|
Exposure
C
|
|||||
|
(1)
|
(2)
|
(1)
|
(2)
|
|||
|
4
in.
|
4
in.
|
65
|
6
ft.
|
(2.5
ft.)*
|
6
ft.
|
(1.5
ft.)*
|
|
4
in.
|
6
in.
|
74
|
6
ft.
|
(5
ft.)*
|
6
ft.
|
(2.5
ft.)*
|
|
4
in.
|
8
in.
|
80
|
8
ft.
|
(8
ft.)*
|
6
ft.
|
(4.5
ft.)*
|
|
4
in.
|
10
in.
|
88
|
11
ft.
|
(11
ft.)*
|
7
ft.
|
(7
ft.)*
|
|
4
in.
|
12
in.
|
96
|
27
ft.
|
(27
ft.)*
|
18
ft.
|
(18
ft.)*
|
| *See subrule (8) of this rule. | ||||||
| (8) | If employees within the collapse area are working from elevations that are lower than the bottom elevation of the wall, the maximum unsupported height of a masonry wall shall be determined from values given in column (2) of tables 2 to 5. |
| (9) | No one shall be permitted within the collapse area of an unbraced or braced wall subjected to winds of more than 35 miles per hour. |
| Return to Table of Contents | |
| R 408.40205 Wind velocity; determination by qualified person. | |
| Rule 205. | For the purpose of this part, the wind velocity shall be determined by a qualified person. |
| Return to Table of Contents | |
| R 408.40206 Wall bracing design. | |
| Rule 206. (1) | When the height of a masonry wall exceeds the maximum unsupported height as shown in tables 2 to 5 of R 408.40204, the masonry wall shall be braced on both sides upon completion. Crosswalls are acceptable instead of bracing an interior wall if the crosswalls are not spaced more than 20 feet apart. If crosswalls are spaced more than 20 feet apart, wall bracing in accordance with the requirements shall be provided. |
| (2) | On masonry projects that require temporary bracing, the wall bracing system shall be determined before a masonry wall exceeds the maximum unsupported height limits specified in tables 2 to 5 of R 408.40204. |
| (3) | The wall bracing system for a masonry wall shall be designed by a qualified person in accordance with acceptable engineering practices or as prescribed in this part and shall be capable of providing stability to the wall for a wind with a velocity of 35 miles per hour. |
| (4) | If pilasters, buttresses, or other reinforcing is part of the wall design, the unsupported height of walls according to tables 2 to 5 of R 408.40204 may be exceeded by complying with accepted engineering practices. Calculations or plans and specifications shall be available at the jobsite. |
| (5) | If scaffolding, because of work operations, remains erected on 1 side of the completed wall, the collapse area shall be identified and marked. No one shall be permitted within the collapse area when the wind velocity is more than 35 miles per hour. |
| (6) | The height of a masonry wall above the intersection of the diagonal support with the vertical plane of the wall shall not be more than the maximum unsupported height as shown in tables 2 to 5 of R 408.40204. |
| Return to Table of Contents | |
![]() |
| (6) | The maximum spacing for typical exterior wall bracing shall not be more than 20 feet. Table 6 specifies typical exterior wall bracing requirements and reads as follows: |
|
TABLE 6 |
|
|
Typical
Exterior Wall
|
|
|
8
inch wall
|
18
feet maximum height
|
| 12 inch wall | 22 feet maximum height |
| Return to Table of Contents | |
![]() |
| Rule 209. | An unsupported masonry wall, including the wall bracing system, shall be inspected for damage by a qualified person after each windstorm if the wind velocity was more than 35 miles per hour. If any movement of the wall or other physical damage, including damage to the wall bracing system, is found, only those persons repairing the wall or wall bracing system shall be permitted to work within the collapse area until repairs have been made. |
| Return to Table of Contents | |
| R 408.40210 Wall bracing system; responsibility for installation; responsibility for replacing system and danger signs. | |
| Rule 210. | The masonry contractor shall be responsible for the initial installation of the wall bracing system. After a wall bracing system and danger signs have been installed in accordance with the provisions of this part, any party, including a subcontractor, general contractor, or owner, who alters or removes the bracing system or danger signs shall be responsible for replacing the bracing system and danger signs in accordance with the provisions of this part. |
| Return to Table of Contents | |