If a building or property is located within the lateral inclusion zone (LIZ), if a site-specific approach is implemented, or if there are conduits that a vapor source can enter and will directly transport vapors to a building, then data collection is needed to evaluate VIAP risks. The data collection should be based on where the vapor source is in relation to the building and the transport mechanism for vapors to enter the building. The following sections discuss the data collection in detail:
- Building over Vapor Source (Section C.3 1.0)
- Vapor Source not in Contact with a Building
- Vapor Source in Contact with a Building
- Building adjacent to a Vapor Source (Section C.3 2.0)
- Utilities (Section C.3 3.0)
- Vapor Source within Utility Backfill Material
- Vapor Source in an Underground Conduit
- Buildings are Not Currently Present (Section C.3 4.0)
- Redefining the LIZ (Section C.3 5.0)
Types of Soil Gas Samples
The investigation approach after the vapor source has been adequately delineated will include soil gas sampling if appropriate. Representative soil gas data allows for better risk-based decisions since soil gas data reflect the processes that are occurring at the water table and in the vadose zone (e.g., partitioning, sorption). Three primary options are available for evaluating and characterizing soil gas which differ by the sampling location relative to the building under investigation (if present):
- Sub-slab soil gas. These sampling points are located within the footprint of a building and are installed by drilling through the slab. They are not located outside of a building and require an actual building to be present. Sampling depths are less than one (1) foot below the bottom of the slab. They are the most representative and predictive of vapors located beneath the building and their potential to cause an unacceptable health risk.
Note: Sub-slab soil gas samples are preferred over exterior samples for a building evaluation unless the lateral migration of vapors is being evaluated. More information and methods for collecting soil gas samples and additional factors in sample placement are described in Volume 2 – Investigation Methods for the Volatilization to Indoor Air Pathway.
- Exterior Soil Gas. These subsurface sampling points are located at some distance (usually ten (10) linear feet or more) away from the building. Sample points are installed within the vadose zone and ideally at least five (5) feet below the ground surface. Factors considered for selecting sampling depth include (1) fluctuations in water table depth; (2) thickness of capillary fringe; (3) minimum sampling depth; and (4) depth of the vapor source. See Volume 2 – Investigation Methods for the Volatilization to Indoor Air Pathway for other depth considerations.
- Near-Slab Soil gas. These subsurface sampling points are located around the perimeter of the building (typically less than five (5) feet horizontally from a building). In addition to the sampling depth considerations for external soil gas points, building features (such as depth of foundation) should be considered when selecting near-slab sampling depths. Sub-slab soil gas samples are preferred over near-slab soil gas samples unless lateral migration is evaluated. Near-slab samples are typically used to evaluate the fill associated with a utility line or the lateral migration of vapors and the vapor source is close to the building (see Section C.3 2.0)
Note: Pressure differential readings, as well as O2, CO2, and methane, should be collected prior to any soil gas samples being collected to aid in CSM development and to ensure that the pressure gradient is from the subsurface into the building.
General advantages and disadvantages for each type of vapor sampling method for the investigation of a release is provided in Table C.3 – 1. More information is available in Volume 2 – Investigation Methods for the Volatilization to the Indoor Air Pathway.
Table C.3 – 1: Advantages and Disadvantages of Various Investigative Strategies
|
Measurement |
Advantages |
Disadvantages |
Comments |
|
Sub-slab soil gas |
|
|
|
|
Near-Slab Soil Gas (e.g., typically, |
|
|
|
|
Exterior Soil Gas (>5-feet below grade) |
|
|
|
|
Exterior Shallow Soil Gas (3-5-feet below grade) |
|
|
|
|
Exterior Shallow Soil Gas (<3-feet below grade) |
|
|
|
Vertical soil gas profiles can be acquired by installing a series of nested or clustered exterior or near-slab soil gas points at a range of depths. This may be useful in the development of site-specific risk evaluations. Additional information on vertical soil gas profiles can be found in Volume 2 – Investigation Methods for the Volatilization to Indoor Air Pathway.