The Michigan Department of Licensing and Regulatory Affairs (LARA) will never ask you to provide credit card numbers or other personal information by phone, text, email, or mail. LARA has identified fraudulent communications impersonating department staff. These scams may include requests for payment or personal information. Please do not respond to these messages and report any suspicious activity to LARA‑Safety@michigan.gov. (This email is for fraud purposes only; messages unrelated to LARA‑related fraud will not receive a response.)
Notice to Owners and Installers of B31.1 Non-Boiler External Pipe
Michigan Department of Licensing and Regulatory Affairs
Pursuant to 2010 ASME Boiler and Pressure Vessel Code B31.1, Chapter VI, 136 Inspection and Examination, Section 136.1.1 states in part that an "inspection is the responsibility of the Owner and may be performed by employees of the Owner or a party authorized by the Owner….”
Additionally, Section 136.1.4(A) states in part that “the Owner’s Inspector shall be designated by the Owner and shall be an employee of the Owner, an employee of an engineering or scientific organization, or of a recognized insurance or inspection company acting as the Owners agent.” The State of Michigan Chief Inspector or Deputy Inspectors will not perform power piping inspections.
Section 136.1.1 further states that “prior to initial operation, a piping installation shall be inspected to ensure compliance with the engineering design and with the material, fabrication, assembly, examination, and test requirements of [ASME B31.1-2010].” Such inspections and inspectors shall be in compliance with ASME B31.1, Chapter VI, 136 Inspection and Examination.